SLC TWIN PRO

Short description

Covering a wide range of powers from 700 VA to 20 kVA, J.Schneider SLC TWIN PRO series gives maximum reliability in electrical protection for businesses and industry. With its double conversion On-line technology, the most reliable technology on the market, the SLC TWIN PRO series is a single phase output UPS (with single phase input from 700 VA to 10 kVA and three-phase input from 8 kVA to 20 kVA), with an output power factor of 0.9(1), broad communication options via interface + monitoring/automatic file closing shutdown software, batteries for standard autonomy integrated in the cabinet itself, option of extending back-up for processes requiring greater available autonomy and options of parallel/redundant operation up to 4 units(1) for installations growing in qualitative and quantitative demands.

Added performances include the standard static and maintenance bypasses(1), the low input current distortion (THDi) under 5%, small footprint in both standard and extended autonomies, full information obtained from the LCD/graphic display or the possibility of working in frequency converter mode.

Request infos about this product

Product request

Start your request for this product!
captcha

Technical Data

Model

TWIN PRO 0,7 ÷ 3 kVA

TWIN PRO 4 ÷ 10 kVA

TWIN/3 PRO 8 ÷ 20 kVA

FORMAT

Tower

TECHNOLOGY

On-line, double conversion, PFC with double DC bus

INPUT

Nominal voltage

200 / 208 / 220 / 230 / 240 V (1)

3 x 380 / 400 / 415 V

 

Voltage range

110 ÷ 300 V (2)

110 ÷ 276 V (2)

3 x 190÷478+N (2)

 

Frequency

50 / 60 Hz

 

Frequency range

± 10%

 

Power factor

≥ 0,99

 

Total Harmonic Distortion (THDi)

<5%

OUTPUT

Power factor

0,8

0,9

 

Nominal voltage

200 / 208 / 220 / 230 / 240 V (1)

 

Voltage accuracy

± 2%

± 1%

 

Maximum slew rate

1 Hz/s

 

Frequency
synchronisation

mains present  

± 10%

 

free running

± 0,2 Hz

± 0,1 Hz

± 0,05 Hz

 

Efficiency

>88%

92%

>93%

 

Total Harmonic Distortion (THDv) (2)

≤3% linear load;
≤5% non-linear load
(according to EN 62040-3)

≤2% linear load;
≤5% non-linear load
(according to EN 62040-3)

 

Admissible overload
(normal mode)

Up to 110% during 1 min;
125% during 30 s

Up to 125% during 2 min;
150% during 30 s

Up to 110% during 5 min;
130% during 1 min

 

Crest factor

3 to 1

 

Parallel

No

Yes, up to 4 units

 

(1) Power reduction for 200 V and 208 V versions in single-single units and only for 200 V in three-single

(2) With load at 50%

(3)Power reduction of 40% in single-single models

(4) 8 kVA and 10 kVA <55 dB

More details see flyer.

Downloads

Description

Version

File Format

Flyer SLC TWIN PRO

-

PDF

Manual 0,7 ... 3 kVA

-

PDF

Manual 4 ... 20 kVA

-

PDF

To download the manuals please log in here

Questions?