Ultracapacitor buffered Power Supply

Type:
AC-C-TEC 2410-10
Art.-No.:
NCPA1430G01001

Short Description

The DC-UPS of the series AC C-TEC 2410-10 includes ultra-capacitors as energy storage inside the housing. During normal operation the capacitors are charged from an internal charger, which is supplied by an internal, regulated AC-DC power supply. In case of an interruption of the AC supply, the energy of the ultra-capacitors is released regulated (23,5 V DC ± 5%). The load is supplied by the back-up module up to the ultra-capacitors are discharged. The back-up time depends on the state of charge of the capacitors and on the discharge current

The DC-UPS has the following characteristics:

  • Maintenance-free because of long-life ultra-capacitors
  • Microcontroller based charging and discharging of the ultra-capacitors
  • Parameterizable via USB interface
  • Control of operation and status of charge with potential-free contacts and LED
  • Big temperature range -20 °C up to 50 °C

Request infos about this product

Product request

Start your request for this product!
captcha

Technical Data

Input voltage range

100 V - 240 V AC

100 V - 230 V DC

nominal frequency

50 Hz … 60 Hz ± 6 %

Max. nominal input current

1,11 A @ 230 V AC

2,35 A @ 110 V AC

Max. inrush current

1,76 A

nominal Output current (in mains operation)

24,1 V DC ± 2 %

Output current range (in buffer operation)

23,5 V DC ± 5 %

Max. nominal Output current

10 A DC

efficiency

> 90 %

energy

10 kJ

back-up time

400 sec @   1 A  

  42 sec @ 10 A

protective system

IP20 

operational temperature

-20 ... 50 °C 

storage temperature

-20 ... 60 °C 

Relative humidity

95 % non condensating

Max. mounting heigth (without derating)

2000 m above sealevel

dimensions (H x W x D)

163 mm x 189 mm x 138mm  

weight

ca. 3,0 kg 

Norms and Regulations

EN 50178 

UL-registration

No

 For more details see datasheet.

Downloads

DescriptionVersion
File Format

Datasheet

150226PDF
Manual100220PDF
Eplan Macroedz

To download the manual and the eplan macro please log in here