DC-UPS with Batteries

Type:
AKKUTEC 2405
Art.-No.:
NBPA0616G01101

Short description

The battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.
The back-up time is depending from the state of charge of the accumulator and of the discharge current.


The power supply has the following features:

  • Battery charger with I/U-charging characteristics

  • Battery management by micro-controller

  • Battery voltage tracking of the charging voltage by external sensor module (optional)

  • USB interface: with corresponding drivers and Schneider TECControl Software the message contacts can be controlled and a Shut-Down/Restart can be made.

Request infos about this product

Product request

Start your request for this product!
captcha

Technical Data

Nominal input voltage

115 ... 230 V AC -15% +10%

Nominal frequency

47 ... 63, Hz

Max. nominal input current

Max charging current

0,5 A

Nominal output voltage

24 V DC

Output voltage range (with temp.-sensor)

19,8 V DC ... 27,8 V DC

Output voltage range (without temp.-sensor)

19,8 V DC ... 26,8 V DC

Max. nominal output current

5 A DC

Charge end voltage with temp.-sensor @ 25°

27,1 V DC ± 0,4%

Charge end voltage without temp.-sensor

26,8 V DC ± 0,4%

Efficiency

88,0 %

Battery type

Pb-Akku, maintenance-free

Pb- Akku maintenance-free (Option with changed characteristic)

Buffer time

Depending on battery and load

Degree of protection

IP 20

Operating temperature

0 ... 40 °C

Storage temperature

Relative humidity

Max. altitude (without derating)

Dimensions (H x W x D)

160 mm x 75 mm x 150 mm

Weight

approximately 1,6kg

Norms and Regulations

EN 50178 / EN60950

UL approvals

UL 508

C22.2

For more details see datasheet.