The battery buffered DC power supply is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply during a determined time interval in case of mains failure. The total output current is shared between supply of the loads and charging of the batteries.

Request infos about this product

Product request

Start your request for this product!
captcha

Technical Data  

Nominal input voltage

110/230 V AC (±15%)

Input voltage range for charging operation

93.5 V … 264.5 V

Nominal frequency

47 Hz … 63 Hz

Power consumption

90 VA

Self current consumption

100 mA @ 24 V

Max. nominal input current

0.5 A

Max. inrush current

35 A / 2 ms

Max. nominal output current

3 A

Nominal output voltage (in mains operation)

24 V DC

Output voltage range (with temperature tracking)

26.4 V … 28.6 V DC ±0.4%

Charging characteristics

I/U DIN41773

Charging end voltage without temp.-Sensor

26.4 V DC ±0.4%

Deep discharge protection and load shedding

20.4 V DC ±0.4%

Max power loss ‚worst-case‘

14 W

Efficiency

85% q (Ue=230 V; Ua=26.4 V DC; Ia=INenn)

Voltage ripple

< 100 mV eff.

Internal device protection

2 A (T), 250 V

Fuse DC-output circuit (external)

5 A(T)

Fuse DC-battery circuit (external)

5 A(T)

Max. signal contact load (mains-OK[1])

30 V/ 0.5 A
potential-free relay-contact

Max. signal contact load (Bat-OK 1)

30 V/ 0.5 A
potential-free relay-contact 

Max. signal contact load (General fault 1)

30 V/ 0.5 A
potential-free relay-contact

Max. signal voltage range (Shut-Down)

24 V DC (6-45 V DC)
floating switching input

Accumulator type

Pb-accumulator, maintenance-free
max 2x26 Ah

Back-up time

Accumulator specific

Protective system

IP30

Operating temperature

-10 °C … 50 °C

Storage temperature

-10 °C … 50 °C

Rel. humidity

≤95% no condensation

Max. installation altitude

2000 m above sea level

Dimensions (HxWxD)

362 mm, 464 mm, 145 mm

Weight

7,5 Kg