The battery buffered DC power supply is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply during a determined time interval in case of mains failure. The total output current is shared between supply of the loads and charging of the batteries.

Request infos about this product

Product request

Start your request for this product!
captcha

Technical Data

nominal voltage:                      

230 VAC (-15% / +10%)

nominal frequency:

47 Hz up to 63 Hz

power consumption:

380 VA, max.

input current    

1.8 A (at 12A output)

inrush current:              

35 A / 2 ms, max.

Output voltage

(depending on the state of charge

of the battery voltage range)

- with temperature tracking

19,8V DC-27,8V DC

- without temperature tracking

19,8V DC-26,8V DC

nominal output current

(incl. battery charging current according to VdS):

 

12 A, max.

deep discharge protection and load rejection:

20,4 VDC, ± 0,4%

final charging voltage

without temp.- sensor

 

26,8 V DC ± 0,4%

with Temp.- Sensor @ 25°

27,1V DC ± 0,4% 

efficiency:                   

89 %

contact load relay:       

30 VDC / 0,5 A, potentialfree relay contact

type of battery:           

lead-acid battery, maintenancefree

environmental temperature:

-5°C up to 40°C (observe life duration of battery)

storage temperature

-5°C up to 50°C

dimensions (HxWxD):  

608mm x 464 mm x 213 mm

weight:

12,5kg without battery

protective system housing:

IP30

fuse mains:

2,5A, slow acting, 250V, switch level 1500A

fuse DC-battery circuit 

15A, FK2 / FKS

fuse consumer:           

single max. 10A, FK2 / FKS, total max. 15A